For each solenoid valve is indicate the flow coefficent Kv.
With this data it is possible to calculate the flow. Known the loss of flowing pressure (pressure drop),
the media type and the working pressure it’s possible to calculate the rate flow.
This coefficent of flow is determined by way of experimentation to the standard VDE 2173 and represents
the discharge of water from the solenoid valve with a pressure difference of 1bar
at temperatures between 5°C and 40°C.
Kv = m3/h
Flow coeffient
Q = m3/h
Flow
Qn = m3n/h
Normal flow (20°C 760mm Hg)
P1 = bar
Inlet pressure
(Gauge pressure + 1)
P2 = bar
Outlet pressure
(Gauge pressure – 1)
DP = bar
Pressure drop
(Differential pressure between
inlet and outlet pressure)
r = Kg/dm³
Relative density with respect to water
(Water at 4°C = 1)
rn = Kg/dm³
Normal relative density as to the air
G = Kg/h
Mass
t = °C
Inlet media temperature
V1 = m3/Kg
Inlet specific volume
V2 = m3/Kg
Outlet specific volume referred to
“P2” pressure and “t” temperature